Nombre De La Marca: | GENY |
Número De Modelo: | Yc1893d |
Cuota De Producción: | 1 PCS |
Precio: | Negociable |
Condiciones De Pago: | L/C, T/T, D/P |
Capacidad De Suministro: | 100/año |
Guangzhou GENY Electric Co., Ltd. is a professional manufacturer of power metering and testing equipment, established in 2002. With the registered brand "GENY", we are known for reliable quality, innovative design, and strong industry expertise.
We focus on R&D and production of electric meter testing systems, serving utilities and industrial users with trusted solutions.
1. Accuracy class : 0.05
2. Easy to calibrate I-P closed links meters with isolated current transformer(ICT)
Technical spec. |
YC1893D-ICT-6 |
YC1893D-ICT-12 |
YC1893D-ICT-24 |
YC1893D-ICT-48 |
Number of meter positions equipped ICT |
6 |
12 |
24 |
48 |
Accuracy class of ICT |
0.05 / 0.01 |
|||
Accuracy |
0.05 |
|||
Power Source |
YCS-103-250 |
YCS-103-600 |
YCS-103-1200 |
YCS-103-2500 |
Standard Meter |
SZ03A-K6 / SZ03A-K8 (customized) |
|||
Scanning Head |
YCG-S Series |
|||
Voltage |
|
|||
Test voltage output(Phase-Neutral) |
3x(24V~288V)(or customized) |
|||
Power of the voltage output |
Max. 3x100VA |
Max. 3x250VA |
Max. 3x500VA |
Max. 3x1000VA |
Resolution |
Better than 0.01% of full scale value of range |
|||
Setting accuracy |
Better than 0.05% at the final range value |
|||
Stability |
Better than 0.005% /h (integration time 150s) |
|||
Load regulation from 0~max. load |
Better than 0.01% |
|||
Distortion factor |
Better than 0.3% for linear resistance load |
|||
Harmonic |
2nd~21st free programmable |
|||
Current |
|
|||
Test current output |
3x(1mA~100A) |
|||
Power of the current output |
Max. 3x150VA |
Max. 3x350VA |
Max. 3x750VA |
Max. 3x1500VA |
Resolution |
Better than 0.01% of full scale value of range |
|||
Setting accuracy |
Better than 0.05% at the final range value |
|||
Stability |
Better than 0.005% /h (integration time 150s) |
|||
Load regulation from 0~max. load |
Better than 0.01% |
|||
Distortion factor |
Better than 0.3% for linear resistance load |
|||
Harmonic |
2nd~21st free programmable |
|||
Phase angle |
|
|||
Range |
0~360⁰ |
|||
Resolution |
0.01⁰ |
|||
Setting accuracy |
0.1⁰ |
|||
Frequency |
|
|||
Range |
45Hz~65Hz |
|||
Resolution |
0.01Hz |
|||
Error display |
|
|||
Type of error display |
Red LED |
|||
Resolution of error displays |
8 digitals |
|||
Other |
|
|||
Voltage supply |
3x220/380V±10%(or customized) 50/60Hz ±2Hz |
|||
Ambient temperature |
-10°C~+40°C |
|||
Relative humidity |
35%~85% |